The pumping station without sewage wastewater is equipped with a submersible pump and a backflow preventer. The collection tank is an LW 1000 chamber system made of permanently resistant polymer (PE) with open pump tank and universal connection options. Quick-release closures enable the integrated components to be removed easily. The station is optionally controlled by a user-friendly control unit, which can be integrated in the building management system via a potential-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface.
Variant
Type of system: duo pump
Passage seal for conduit pipe (DN): 100
Passage seal for ventilation pipe (DN): 100
Installation: Wet installation
Pump control: Control unit
Backwater protection: integrated
Chamber system: Komfort inspection chamber LW 1000
General characteristics
Standard: EN 12050-2
Delivery state: Modular set for assembly on site
System type: Duo
Dimensions
Net weight: 258 kg
Gross weight: 280 kg
Installation depth: 1630 - 2130 mm
Packaging dimension: length: 2200 mm
Packaging dimension: width: 1200 mm
Packaging dimension: height: 1740 mm
Coverage features
Type of cover: Round cover plate
Load class: B 125 (EN 124)
Pumping device
Pump: KTP 1000
Number of pumps: 1
Length of mains cable for pump: 10 m
Protection class (pump): IP 68 (3m)
Operating mode: S3 - 50 %
Impeller type: Multi-vane impeller
Control
Control unit: Comfort
Alarm sensor: optical probe
Level measurement instrument: Submersible pressure switch
Type of level measurement: pneumatic
Protection class control unit: IP 54
Mains frequency: 50 Hz
Operating voltage: 230 V
Length of mains cable for control unit: 1,4 m
Potential-free contact: optional
GSM interface: yes
USB interface: yes
Log book function: yes
Multi-line display: yes
Battery buffering: yes
Self-diagnosis system (SDS): yes