The pumping station for wastewater with and without sewage is equipped with a submersible pump, a backflow preventer and a shut-off valve for the pressure pipe. The collection tank made of permanently resistant polymer (PE) has an open pump tank (wet installation) with universal connection options. The station is controlled by a user-friendly control unit, which can be optionally integrated in the building control system via a potential-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface. The KESSEL modular system provides different engineering chamber options as accessories for the further layout.
Variant
Type of system: duo pump
Shut-off valve: Shut-off valve made of polymer
Passage seal for conduit pipe (DN): 100
Access steps: yes
Passage seal for ventilation pipe (DN): 100
Installation: Wet installation
Pump control: Control unit
Backflow preventer: integrated
Pressure pipe connection: horizontal
General characteristics
Colour: black
Standard: EN 12050-2 as well as EN 12050-1 (without ATEX requirements)
Type of wastewater: for wastewater with or without sewage (in installation situations without ATEX requirements)
Installation situation: underground installation
Delivery state: Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected)
System type: Duo
Dimensions
Vertical adjustment: 2014 - 2263 mm
Net weight: 280,24 kg
Gross weight: 320,86 kg
Groundwater resistant from lower edge of base section: 3000 mm
Packaging dimension: length: 3300 mm
Packaging dimension: width: 1300 mm
Packaging dimension: height: 2200 mm
Tank/drain body
Pressure pipe connection (DN): 80
Pressure pipe connection (OD): 90 mm
Inlet nominal size (OD): 160 mm
Inlet nominal size (DN): 150 mm
Number of inlets: 1
Clear width of entry (LW): 1000 mm
Pumping volume: 340 l
Pumping device
Pump: GTF 1400
Number of pumps: 2
Weight, pump: 22 kg
Connection type: Direct connection
Rated current: 6,5 A
Protection class: I
Insulation class: H
Cos phi - power factor: 0,99
Protection class (pump): IP 68 (20m)
Temperature monitoring: integrated
Max. temperature (permanent) of conveyed material: 40 °C
Max. pumping capacity: 31 m³/h
Max. pumping height: 10,5 m
Speed: 2900 U/min
Power P1: 1,5 kW
Power P2: 1,1 kW
Operating mode: S1
Type of fuse required (electrical protection): C 16 A
Type of pump connection cable: H07RN-F 3G 1.5 mm²
Impeller type: Multi-vane impeller
Free passage: 30 mm
Length of mains cable for pump: 10 m
Control
Control unit: Comfort
Control unit function: With alarm message
Motor protection switch: yes
Alarm sensor: Level sensor
Level measurement instrument: Level sensor
Type of level measurement: hydrostatic
Protection class control unit: IP 54
Mains frequency: 50 Hz
Operating voltage: 230 V
Connection type: Direct connection
Length of mains cable for control unit: 1,4 m
Potential-free contact: optional
GSM interface: yes
USB interface: yes
Log book function: yes
Multi-line display: yes
Battery buffering: yes
Self-diagnosis system (SDS): yes
Warning equipment version: acoustic and optical signal
Type of fuse required (electrical protection): C 16 A