Replacement pump with macerator for faecal wastewater, includes connection adapter for TPF120
Variant
Series: bis 10/2006
General characteristics
Standard: EN 12050-1
Type of wastewater: with sewage
Dimensions
Net weight: 53,33 kg
Gross weight: 60 kg
Packaging dimension: length: 700 mm
Packaging dimension: width: 800 mm
Packaging dimension: height: 620 mm
Pumping device
Pump: TPF 120
Connection type: Direct connection
Operating voltage: 400 V
Mains frequency: 50 Hz
Protection class: I
Insulation class: F
Cos phi - power factor: 0,71
Protection class (pump): IP 68 (3m/48h)
Temperature monitoring: controlled via control unit
Max. temperature (permanent) of conveyed material: 40 °C
Max. pumping height: 16,6 m
Speed: 2885 U/min
Power P1: 1,75 kW
Power P2: 1,3 kW
Operating mode: S1
Type of pump connection cable: H07RN-F 7G 1.5 mm²
Length of mains cable for pump: 10 m
Rated current: 3,56 A
Control
Connection type: Direct connection
Type of fuse required (electrical protection): Fuse protection through control unit 400 V